Fire Curtains and Smoke Curtains Product Matrix
THIRD PARTY CERTIFICATION
Coopers Fire ensure our products conform to the latest standards and regularly carry out testing. Third Party Product Certification Schemes give confidence to specifiers, users, occupiers, owners and enforcement bodies that products have been independently assessed and evaluated and are manufactured using the same specification as originally tested.
Coopers Fire have Third Party Independent Certification through:
IFC Certification Ltd
Warringtonfire Certification Scheme
UL
THE TABLES below WILL HELP ASSIST YOU WITH THE TYPE OF FIRE OR SMOKE CURTAIN PRODUCT REQUIRED.
BS 8524-1 FIRE CURTAINS
Active fire curtain barrier assemblies. Specification.
Products suitable for the UK and other countries
Product Name | Orientation | Max Width and Max Drop | Fire Classification | Certifier | Smoke Control |
---|---|---|---|---|---|
FireMaster A1 Fire Curtain |
Vertical - Single Roller | 7m x 7m 7m x 8m |
E180 EW30 E120 EW30 |
IFC Certification | Yes* |
FireMaster A1 Fire Curtain |
Vertical - Overlapping Rollers | Unlimited x 6m |
E120 EW30 | IFC Certification | No |
FireMaster Plus2 Fire Curtain |
Vertical - Single Roller/Wide Single Roller | Up to 20m max. width x up to 7m max. drop | Up to E180 EW90 (E=Integrity, EW=Radiance) | IFC Certification | Yes* |
FireMaster Concertina Fire Curtain |
Concertina - Open | Unlimited x 2.856m Unlimited x 10m |
E180 EW30 E120 EW30 |
IFC Certification | No |
FireMaster Concertina Fire Curtain |
Concertina - Closed | Unlimited x 2.85m Unlimited x 3.3m Unlimited x 10m |
E240 EW30 E180 EW30 E120 EW30 |
IFC Certification | Yes* |
ViiFire A1 Fire Curtain |
Vertical - Single Roller | 3m x 3m | E120 EW30 | IFC Certification | Yes* |
ViiFire iZone Fire Curtain |
Vertical - Single Roller | 2.6m x 2.8m | E180 EW60 | IFC Certification | Yes* |
* Approved to BS EN 1634-3, Fire resistance and smoke control tests for door and shutter assemblies, openable windows and elements of building hardware. Smoke control test for door and shutter assemblies.
BS EN 1634-1 FIRE CURTAINS
Fire resistance and smoke control tests for door and shutter assemblies, openable windows and elements of building hardware. Fire resistance test for door and shutter assemblies and openable windows
Products suitable for the UK, Europe and other countries
Product Name | Orientation | Max Width and Max Drop | Fire Classification | Certifier | Smoke Control |
---|---|---|---|---|---|
FireMaster A1 Fire Curtain |
Vertical - Single Roller | 6m x 7m 5.2m x 7m |
E120 EW30 E180 EW30 |
Warringtonfire | Yes* |
FireMaster A1 Fire Curtain |
Vertical - Overlapping Roller | Unlimited x 6m | E120 EW30 | Warringtonfire | No |
ResQ-Window Vision Panel |
Vertical - Single Roller | 6m x 8m | E120 EW30 | Warringtonfire | Yes* |
FireMaster Plus2 Fire Curtain |
Vertical - Single Roller | 7m x 7m 7.8m x 6.2m 7m x 4m |
E120 EW90 E120 EW90 E180 EW90 |
Warringtonfire | Yes* |
FireMaster Insul8 |
Vertical - Single Roller | 7m x 3.35m | E240 EW240 EI190 | Contact Coopers Fire | No |
FireMaster Cleanroom Fire Curtain |
Vertical - Single Roller | 4m x 3m 4m x 4m |
E120 EW120 E90 EW90 |
Warringtonfire Fraunhofer |
No |
FireMaster Marine Fire Curtain |
Vertical - Single Roller | 2.4m x 2.692m | A-0 rating. 60 minutes | Lloyds Register | No |
FireMaster Horizontal Simplex Fire Curtain |
Horizontal - Simplex | 7m x 7m | E120 EW20 | Warringtonfire | No |
FireMaster Horizontal Duplex Fire Curtain |
Horizontal - Duplex | 7m Width x 14m High 3m Width x 20m High |
E120 EW15 E60 EW15 |
Contact Coopers Fire | No |
FireMaster 4/1000 Fire Curtain |
Vertical - Single Roller | 7m x 2.5m 7m x 8m |
E240 EW30 E180 EW30 |
Warringtonfire | Yes* |
FireMaster Superplus Fire Curtain |
Vertical - Single/Overlapping Rollers | Unlimited x 3m | E120 EI120 (through assessment) | Contact Coopers Fire | No |
FireMaster Concertina Open Fire Curtain |
Concertina - Open | Unlimited Width x 10m High 5m Width x 5m High |
E90 E60 EW 60 |
IFC Certification | No |
FireMaster Concertina Closed Fire Curtain |
Concertina - Closed | Unlimited Width x 10m High 5m Width x 5m High |
E90 E60 EW 60 |
IFC Certification | Yes* |
FireMaster Concertina Egress Fire Curtain |
Concertina - Closed/Open | Unlimited Width x 10m High 5m Width x 5m High |
E90 E60 EW 60 |
Warringtonfire | No |
ViiFire A1 Fire Curtain |
Vertical - Single Roller | 3m x 3m | E120 EW30 | IFC Certification | Yes* |
ViiFire iZone Fire Curtain |
Vertical - Single Roller | 3m x 3m | E180 EW60 | IFC Certification | Yes* |
* Approved to BS EN 1634-3, Fire resistance and smoke control tests for door and shutter assemblies, openable windows and elements of building hardware. Smoke control test for door and shutter assemblies.
UL FIRE AND DRAFT CURTAINS
UL 10D – Standard for Fire Tests of Fire-Protective Curtain Assemblies
Read more about this standard.
UL 1784 – Standard for Air Leakage Tests of Door Assemblies and Other Opening Protectives
Read more about this standard.
Products suitable for the US, Middle East and other countries
Product Name | Orientation | Max Width and Max Drop | Fire Classification | Certifier | Smoke Control |
---|---|---|---|---|---|
FireMaster A1 Fire Curtain |
Vertical - Single/Overlapping Roller | 2.438m wide x 3.042m High | 4 hr in masonry / 3hr in gypsum | UL | No |
FireMaster Smoke and Fire Barrier |
Vertical - Single/Overlapping Roller | Unlimited x 8m | 180 minutes | Intertek | Yes |
ResQ-Window Vision Panel |
Vertical - Single Roller | 2.43m wide x 3.04m High | 240 minutes in masonry | UL | Yes |
FireMaster Egress Fire Curtain |
Vertical - Single Roller | Contact Coopers Fire | Contact Coopers Fire | Intertek | Yes |
FireMaster Concertina Open Fire Curtain |
Concertina - Open | Unlimited Width x Unlimited High | 180 minutes | UL | No |
FireMaster Concertina Closed Fire Curtain |
Concertina - Closed | Unlimited Width x Unlimited High | 180 minutes | UL | No |
FireMaster Concertina Egress Fire Curtain |
Concertina - Closed/Open | 3.29m width x 3.32m High | 240 minutes | UL | No |
SmokeStop Draft Curtain |
Vertical - Single/Overlapping Rollers | 500' wide x 48' high | N/A | Intertek | No |
SmokeStop Egress Smoke Curtain |
Vertical - Single/Wide Single Roller | unlimited with oversize label | N/A | Intertek | Yes |
BS EN 12101-1 SMOKE CURTAINS
Smoke and heat control systems. Specification for smoke barriers.
Products suitable for the UK and other countries
Product Name | Orientation | Max Width and Max Drop | Certifier | Fire Resistance |
---|---|---|---|---|
SmokeStop D600A Smoke Curtain |
Vertical - Single Roller | Unlimited x 4.840m drop | IFC Certification | 150 minutes |
SmokeStop D600A Smoke Curtain |
Vertical - Overlapping Rollers | Unlimited x 4.840m drop | IFC Certification | 150 minutes |
SmokeStop D600A Smoke Curtain |
Vertical - Side by Side Overlapping | Unlimited x 4.840m drop | IFC Certification | 150 minutes |
SmokeStop DH60 Smoke Curtain |
Vertical - Single Roller | 6.05m x 4m | IFC Certification | 60 minutes (DH60) |
SmokeStop DH60 Smoke Curtain |
Vertical - Overlapping Rollers | Unlimited x 6.3m | IFC Certification | 60 minutes (DH60) |
SmokeStop DH120 Smoke Curtain |
Vertical - Overlapping Rollers | Unlimited x 4.8m | Warringtonfire | 120 minutes (DH120) |
SmokeStop Concertina Open |
Concertina - Open | Unlimited x 6m | Warringtonfire | 60 minutes (DH60) |
SmokeStop Concertina Closed |
Concertina - Closed | Unlimited x 6m | Warringtonfire | 60 minutes (DH60) |
SmokeStop EvacU8 Smoke Curtain |
Vertical - evacU8 | Unlimited x 6.7m | IFC Certification | 150 minutes |